DBDOC-CHECK 800xA DYNAMIC BAR.ERR

The graphic calls for a bargraph to be displayed. However, dynamic value of the bar cannot be displayed by DBDOC because the span is zero. A non-zero value is required to display a bar graph.

The tag involved needs to be corrected so the span is not zero.

In the example, S13 of the MA Station is the SPAN of the Setpoint. However, this is zero, and the dynamic bargraph cannot be displayed correctly.

The picture shows that the bargraph cannot be scaled correctly.

--Scanning graphic U5_ID_FAN_A_SUCTION_PRESS ({A7C00D92-2BA9-404A-8A3E-484F005183D7})
Span is zero for dynamic bar 5-HS-49IDA-32@SP Module 50,52,02 Block 2390 on U5_ID_FAN_A_SUCTION_PRESS -- suppressing.




This error can be built directly into Hyperview. For more information, see the article Building error reports into the M14.