DBDOC-CHECK REMSET OUTSIDE LIMITS.ERR

This message means that the REMSET block FC 68 has an operating value S4 outside the low and high limits S3 and S2. We call this to your attention because the value on a module switchover is outside the legal range. That is, the operator would not be allowed to set the value that the block starts with. This can indicate a potential problem.

--Scanning drawing 1030835
Module 1,03,08 Block 2335 REMSET block S4 value 0.0 is outside configured limits of 80.0 and 120.0.

This error can be built directly into Hyperview. For more information, see the article Building error reports into the M14.