The indicated enhanced input is not a supported type. The documentation indicates that this is a configuration error.
From the documentation for Function Code 179 Enhanced Trend:
S2 (Input block type) Identifies type of input to be trended.
0 = function code 30, analog exception report
1 = function code 45, digital exception report
2 = function code 62, remote control memory
3 = function code 68, remote manual set constant
4 = function code 80, control station
5 = function code 123, device driver
6 = function code 129, multi state device driver
7 = function code 136, remote motor control
8 = function code 177, data acquisition analog
9 = function code 211, data acquisition digital
Note: The block addressed in <S1> must match the input block type in S2 or a configuration error will result.
In this case, S1 is coming from the wrong type of block or S2 should be 3.
This error can be built directly into Hyperview. For more information, see the article Building error reports into the M14.