Spec | Description |
---|---|
S1 |
|
S2 | Minimum exception report time (250 millisecond increments) |
S3 | Maximum exception report time (250 millisecond increments) |
S4 | Significant change loop reports (percent span) |
S5 | Alarm deadband high/low reports (percent span) |
S6 | Alarm deadband deviation reports (percent span) |
S7 | Watchdog timeout interval (2.56 second increment) |
S8 | Update time (same PCU, 250 millisecond increments) |
S9 | Minimum cycle time algorithms (10 millisecond increments) |
S10 | Unlock/lock configuration |
S11 | PID derivative gain (maximum) |
S12 | PID normal/external reset function |
Block | Type | Description |
---|---|---|
240 | Bit | Start-up in progress:
|
241 | Bit | Initialize mode non-volatile RAM:
|
242 | Bit | General purpose switch state |
243 | Real | Last control cycle time (seconds) |
244 | Bit | Slave module valid time |
245 | Real | Current hour (0-23) |
246 | Real | Current minutes (0-59) |
247 | Real | Current seconds (0-59) |
248 | Real | Current year (0-99) |
249 | Real | Current month (0-12) |
250 | Real | Current day (1-31) |
251 | Real | Current day of week (1-7, Sunday = 1) |
252 | Real | Revision level |
253 | Real | Non-volatile RAM utilization (percent) |
254 | Real | RAM utilization (percent) |